Fibre, Connectors & Cabling
Single-mode fibre engineered to tolerate tight bends without leaking light — what patch cords and FTTH drops are made of.
Standard single-mode fibre leaks light when it is bent tightly. At the outside of a curve the guided mode can no longer be supported by total internal reflection and part of it radiates into the cladding. In a patch panel, a riser or a wall box, tight bends are unavoidable, and the resulting macrobend loss is a common and frequently misdiagnosed cause of link failure.
G.657 changes the refractive index profile — usually by adding a depressed trench around the core — so the mode is held more tightly and survives radii that would badly degrade ordinary G.652.D fibre.
Category A is defined to be fully compliant with G.652.D, so A1 and A2 splice and mate into existing plant with no penalty worth measuring. A1 is specified to a 10 mm minimum radius, where a single turn costs no more than 0.75 dB at 1550 nm; A2 goes to 7.5 mm at 0.5 dB per turn, and at 10 mm is an order of magnitude better than A1 at 0.1 dB.
Category B is a different bargain. B2 and B3 are described as compatible with G.652.D rather than compliant — they will not cause system trouble, but their dispersion and PMD attributes are allowed to differ. B3 is rated to a 5 mm radius, which is what makes fibre that can be routed round a corner of a wall box at all.
Use A1 or A2 anywhere the fibre joins the wider plant, which in practice means patch cords, pigtails and distribution cable. Reserve B-class for tightly confined terminations where nothing else physically fits — drop cable stapled round architrave, compact wall outlets, small closures.
Note that bend-insensitive fibre has a diagnostic cost as well as a benefit: because it does not leak, a tight bend that would once have shown up as a clear OTDR event may now be nearly invisible, while still stressing the glass mechanically.
Almost every patch cord made today, all FTTH drop cable, and anything routed inside a cabinet. Most of our patch cords are built on G.657.A1 or A2 as standard, and the FTTH drop cable uses bend-insensitive glass throughout — see the drop cable installation guide. In a dense panel the bend radius is the real constraint, not the fibre grade.
| Categories | A1, A2 (G.652.D compliant); B2, B3 (compatible, not compliant) |
|---|---|
| A1 minimum bend radius | 10 mm |
| A1 at 10 mm, one turn | ≤ 0.75 dB at 1550 nm, ≤ 1.5 dB at 1625 nm |
| A2 minimum bend radius | 7.5 mm |
| A2 at 7.5 mm, one turn | ≤ 0.5 dB at 1550 nm, ≤ 1.0 dB at 1625 nm |
| A2 at 10 mm, one turn | ≤ 0.1 dB at 1550 nm |
| B2 / B3 minimum bend radius | 7.5 mm / 5 mm |
| Mode field diameter, category A | 8.6 to 9.5 µm at 1310 nm |
| For contrast, G.652.D | specified at 30 mm radius over 100 turns |